DATAKOM SMPS-1210 Flyback Battery Charger
DATAKOM SMPS 1210-FLYBACK series are fixed output voltage, current limited lead acid battery chargers specially designed for use in gensets. Thanks to their continuous DC outputs they may also be used in a vide range of industrial applications where DC power is required.
The chargers are designed for permanent connection to genset starter batteries. When the battery voltage is below the float charge level, the charger provides constant current, nearly equal to the rated output current allowing a rapid recovery of the missing charge. When the battery voltage reaches the float level, the charger switches to constant voltage charge mode and maintains the battery fully charged, providing the maximum battery life, without overcharging or gassingLess
The unit has overload and short circuit protections. This feature makes the units deliver only the rated current during engine cranking or a short circuit condition. They do not need disconnection during cranking. The high temperature protection of the unit reduces the output current in case of overheating. Thanks to their high efficiency, the self-heating of the chargers is kept in minimum levels allowing operation in warm environments.
The wide input voltage range allows the chargers to be used in most countries.
The rectifier fail output is provided as a standard feature. This is a semiconductor output pulling to battery negative when the unit is not operating. Thanks to this output, a rectifier fail signal is provided for the genset control module which will give an alarm in case of failure.
The units provide a “boost charge” input as a standard feature. When this input is pulled to battery negative, the output voltage of the charger will be set to the boost charge voltage. This feature may be used temporarily to improve battery life